Emergency Shower and Eyewash Station Maintenance Procedures

Herbert Post
eyewash station maintenance

In 2010, an employee at a semiconductor manufacturing facility was cleaning an acid station. While using a nitrogen gun to clear chemical residue from a sink, a mixture of hydrofluoric acid (HF), nitric acid (HNO₃), and deionized (DI) water splashed into her eyes. Fortunately, a working eyewash station was nearby, and she used it immediately. Paramedics later transported her to the hospital, where she was treated and released the same day without serious complications.

This is one of many examples that highlight why emergency shower and eyewash stations must be properly maintained. If the unit had been obstructed or non-functional, the outcome could have been far more serious. Routine inspection and maintenance of emergency shower and eyewash equipment help prevent chemical injuries from becoming long-term health problems.

Key Takeaways

  • Without regular flushing, sediment and bacteria can build up in eyewash stations, leading to clogged nozzles, poor fluid flow, and unsafe flushing fluid.

  • Unmaintained emergency stations can worsen injuries, as corroded nozzles or poor water quality may cause further contamination.

  • Weekly and annual testing helps identify issues early, keeping eyewash and shower equipment ready and reliable in emergencies.

  • Annual inspections should be performed by qualified personnel familiar with equipment standards and regulatory requirements.

  • Inspection tags show when a unit was last checked, who inspected it, and whether follow-up is needed, supporting consistent maintenance.

 

Importance Of Regular Eyewash Station Maintenance

The case study described earlier shows how emergency eyewash stations directly impact worker safety. When equipment is working, injuries can be managed. When it's not, the risks increase. Regular maintenance makes sure these units are ready when needed. Here are four practical reasons to keep maintenance consistent:

Prevents Contamination

According to an article published by the Occupational Safety and Health Administration (OSHA), Health Effects from Contaminated Water in Eyewash Stations, eyewash equipment that isn’t properly maintained can become a source of infection. Stagnant water in these systems may support the growth of harmful microorganisms such as Acanthamoeba, Pseudomonas, and Legionella. These pathogens are known to cause serious eye and skin infections.

Since eyewash nozzles and showerheads are often exposed to open air and surrounding contaminants, regular flushing is necessary to prevent the buildup of debris, chemical residue, and microbial contamination. Scheduled maintenance keeps the units sanitary and safe for immediate emergency use.

Prevents Sediment Buildup

Plumbing lines connected to emergency eyewash and shower units can develop sediment buildup, particularly in older facilities or areas with hard water. Without regular flushing, this sediment can clog nozzles or restrict water flow. In an emergency, that could delay or even prevent the unit from working properly. 

According to OSHA’s interpretation of 29 CFR 1910.151(c), the valve must activate in one second or less and stay on without the user needing to hold it. Sediment buildup puts that reliability at risk.

Ensures Equipment Functionality

Eyewash stations, self contained eyewash stations, safety showers, or combination units must work immediately and effectively when activated. Weekly and annual testing helps identify problems such as low water pressure, valve malfunctions, or inconsistent spray patterns. Catching these issues early means they can be corrected before someone needs the unit in a real emergency.

Minimizes Equipment Damage

Just like any mechanical equipment, parts in eyewash stations, such as valves, nozzles, and actuators, can wear out or become stuck if left unused. Regular flushing keeps moving parts from seizing and helps detect signs of corrosion, leaks, or mechanical failure before they lead to larger problems or costly replacements.

 

Weekly Maintenance Procedures

OSHA eye wash station maintenance requirements reference ANSI Z358.1-2014, which calls for weekly activation of plumbed units. The goal of weekly checks is to confirm that eyewash and shower equipment are clean, working properly, and immediately usable in case of exposure. Following a consistent inspection and maintenance routine helps catch issues early and keeps the equipment compliant and reliable:

Verify Station Location and Accessibility

Emergency eyewash and shower stations must be maintained in accessible, clearly marked locations. Make sure the unit is located within 10 seconds (roughly 55 feet) of any area where injurious corrosive materials are used. Maintenance should also include ensuring walkways are free from obstacles, spills, or tripping hazards that could delay access to the station. Stations placed too close to boilers, furnaces, or other high-temperature systems may cause the flushing fluid to warm beyond the tepid range.

Inspect Eyewash Nozzles and Showerhead

Visual inspections should check for blockages, corrosion, or physical damage, and ensure nozzle covers are intact and working correctly. Eyewash nozzle covers should lift automatically when the unit is activated, without needing hands. For both eyewash nozzles and showerheads, clean any mineral buildup with a mild detergent and disinfect as necessary to prevent bacterial growth. Any damaged or worn parts must be replaced promptly to maintain effective operation.

Test Water Quality and Flow Rate

Activate the unit and let it run long enough to flush out any stagnant water, typically at least one minute. The water should run clear and be free of discoloration, odor, or debris. Some workplaces even go beyond the weekly standard. As one lab assistant noted in an online forum,

Comment
byu/DIzzy13579 from discussion
inmedlabprofessionals

While daily flushing may not be necessary in all settings, this comment reflects a common concern: sediment or bacterial growth in unused lines. Regular flushing helps keep the water clean and safe for use, especially in environments where water quality is unpredictable.

For portable self-contained eyewash stations, however, weekly activation is not required. Instead, a visual inspection and confirmation of accessibility and expiration dates is typically sufficient to meet maintenance expectations.

Confirm Hands-Free Activation Functionality

Verify that the activation mechanisms, such as push handles, foot pedals, or pull rods, trigger the flow immediately and stay on without manual assistance. Moving parts may require occasional lubrication to prevent sticking. Any malfunctioning components should be repaired immediately to ensure full compliance and readiness during emergencies.

 

Annual Maintenance Checks

While weekly checks focus on basic functionality, annual inspections take a more in-depth look at the condition and performance of emergency eyewash and shower stations. These inspections are an opportunity to identify underlying issues that may not be visible during routine checks.

Perform Flow Rate and Pressure Testing

According to ANSI standards, the stream should be steady and meet the required flow rate of 0.4 gallons per minute for eyewash and 20 gallons per minute for safety showers. Water temperature should remain between 60°F and 100°F to prevent thermal shock or burns. Flow inconsistencies aren't always obvious without proper testing. A professional in an online safety forum shared a telling experience:

Comment
byu/WyldC03 from discussion
inmaintenance

Issues like this aren’t visible during a quick visual check. Comprehensive testing helps uncover hidden blockages, pressure drops, or other small faults that could prevent the unit from working when it’s most needed.

Check for Leak-Free Plumbing Connections

Inspect all visible plumbing connections around the eyewash and shower unit, including valves, supply lines, and joints. There should be no signs of dripping, corrosion, or water accumulation. Even small leaks can lead to pressure loss or unexpected equipment failure.

Also, check the drainage system. Water should flow away from the unit efficiently without pooling around the base. Standing water near eyewash or shower stations can create slip hazards and may indicate a clogged or improperly designed drain.

Test Valve Functionality and Inspect for Integrity

Inspectors must operate each valve to confirm it opens and closes fully without resistance or delay. They must activate within one second and remain in the “ON” position without needing to be held. Additionally, they should assess the physical integrity of the valve body and seals to ensure there are no cracks, corrosion, or signs of wear that could lead to failure.

Inspect the Structural Integrity of the Unit

Examine the physical components of the unit, including pipes, mounting brackets, foot pedals, push handles, and bowl integrity. Look for signs of rust, cracks, or loose fittings. Environmental exposure and operational wear can take a toll on the structure over time, so a careful evaluation helps prevent failures that could pose safety hazards or require costly repairs.

Verify Signage Visibility and Station Accessibility

All eyewash station signs should be reviewed to ensure they are legible, properly mounted, and not faded or damaged. Over time, signs can fade, fall off, or be obscured by new equipment or structural changes. According to ANSI Z535.2-2023, compliant signage should remain clearly visible and easy to understand.

It is recommended that annual maintenance be carried out by qualified personnel, either internal safety staff trained on ANSI requirements or certified third-party professionals. These individuals are better equipped to perform detailed tests, make adjustments, and identify wear that could impact performance over time.

 

Emergency Eyewash Station Maintenance Checklist

Use this checklist to guide both weekly inspections and annual maintenance of emergency eyewash and shower stations. Keeping accurate records of each inspection supports regulatory compliance and improves equipment reliability.

Inspection Item

Yes / No

Comments / Action Needed

Is the unit located within 10 seconds (or ~55 feet) of the hazard area?

/


Is the path to the unit completely clear of obstacles?

/


Is the station positioned away from high-temperature equipment?

/


Is the station clearly visible and not visually obstructed?

/


Are dust covers in place and free from contamination?

/


Are the nozzles clean and free of buildup or debris?

/


Does the unit produce an even, controlled spray pattern?

/


Was the unit flushed for at least one minute during this inspection?

/


Did the water run clear, with no odor or discoloration?

/


Was water pressure steady throughout the flush?

/


Does the activation mechanism work immediately (within 1 second)?

/


Does the valve remain open without needing to be held?

/


Are there any leaks at pipe connections or around valves?

/


Is the drain system functioning properly (no overflow or blockage)?

/


Is the station signage clean, visible, and ANSI-compliant?

/


 

Emergency Shower and Eye Wash Station Maintenance Log

Maintaining accurate and up-to-date records of all inspections, tests, and repairs provides a documented history that can be referenced during audits, safety reviews, or after an incident. A maintenance log should include the following details:

    • Date of inspection or maintenance

    • Type of check (weekly, annual, or corrective)

    • Name of inspector or technician

    • Station ID or location

    • Findings or observations

    • Corrective actions taken (if any)

    • Follow-up required (if applicable)

In addition to centralized logs, inspection tags should be attached directly to each emergency shower and eyewash unit. These tags provide at-a-glance confirmation that inspections are being performed and allow staff to see the last inspection date without checking a separate log.

 

Common Issues In Eyewash Maintenance

During safety inspections at multiple job sites, I’ve consistently observed a set of recurring issues with emergency eyewash and shower equipment. Below are the most common problems and the preventive maintenance steps that can help avoid them:

  1. Low Water Pressure: Weak flow may result from sediment buildup, partially closed valves, or upstream plumbing restrictions. During testing, weak or inconsistent flow should trigger immediate investigation.

  2. Inconsistent Spray Patterns: Blocked or dirty nozzles can cause uneven or misdirected streams. Clean or replace the nozzles to restore proper spray coverage.

  3. Drainage Problems: Water pooling around the unit often indicates a clogged or undersized drain. Clear the drain and ensure it can handle full flow for 15 minutes.

  4. Stiff or Non-Functional Activation Mechanisms: Lack of regular use or exposure to dirt, humidity, or chemicals can cause mechanical parts to seize up. Lubricate or replace moving parts and test the operation regularly.

  5. Other Issues In Special Settings

    1. Outdoor or Remote Locations: Outdoor or high-temperature environments can affect water temperature or equipment reliability. Use insulated piping, heated units, or temperature control valves to maintain safe operation.

    2. Extreme Temperature Environments: Facilities with furnaces, ovens, or industrial heat sources can expose eyewash water lines to high ambient temperatures. In these cases, temperature control valves or insulated lines may be necessary.

I always emphasize that safety equipment only works if it's properly maintained. A consistent inspection schedule, thorough documentation, and prompt corrective action help employers stay compliant and reduce the risk of serious injuries or fatalities on the job.

 

FAQs on Eyewash Station Maintenance

What are the OSHA requirements for eyewash maintenance?

OSHA references ANSI Z358.1 for maintenance standards. This includes weekly activation and annual inspections to verify compliance with flow rate, accessibility, and functionality.

Who is responsible for inspecting and maintaining the stations?

Employers are responsible for ensuring that qualified personnel, such as safety officers or trained maintenance staff, conduct regular inspections and servicing. Clear documentation should be kept to show compliance.

How often should eyewash stations be checked?

ANSI Z358.1 recommends weekly activation of plumbed eyewash stations and a comprehensive annual inspection. These intervals are widely accepted as the standard under OSHA’s interpretation of maintenance requirements.

What should I do if the water flow is weak or uneven?

First, check for blockages, sediment buildup, or valve issues; flush the unit and inspect nozzles. If the problem persists, repair or replace the affected components to meet ANSI flow standards.

What are the signs that an emergency station is non-compliant or unsafe?

Signs include low or no water pressure, clogged nozzles, missing signage, slow valve activation, obstructed access, or visible damage. Any of these issues can make the unit unreliable during an emergency and should be addressed immediately.


The material provided in this article is for general information purposes only. It is not intended to replace professional/legal advice or substitute government regulations, industry standards, or other requirements specific to any business/activity. While we made sure to provide accurate and reliable information, we make no representation that the details or sources are up-to-date, complete or remain available. Readers should consult with an industrial safety expert, qualified professional, or attorney for any specific concerns and questions.

Herbert Post

Born in the Philadelphia area and raised in Houston by a family who was predominately employed in heavy manufacturing. Herb took a liking to factory processes and later safety compliance where he has spent the last 13 years facilitating best practices and teaching updated regulations. He is married with two children and a St Bernard named Jose. Herb is a self-described compliance geek. When he isn’t studying safety reports and regulatory interpretations he enjoys racquetball and watching his favorite football team, the Dallas Cowboys.