OSHA 1910.333 and 1910.147 address different hazards, but one maintenance job can involve both. One covers electrical work practices; the other controls hazardous energy during covered machine servicing and maintenance. The distinction affects written procedures, isolation devices, and verification. This guide explains where each rule applies, when one procedure can satisfy both, and what safety teams should confirm before work begins.
Key Takeaways
- OSHA 1910.333 covers electrical work practices, including lockout and tagging of fixed electrical equipment and circuits under paragraph (b)(2).
- OSHA 1910.147 covers hazardous-energy control during qualifying machine servicing and maintenance, including electrical and non-electrical sources within its scope.
- A procedure that meets 1910.147 can also satisfy 1910.333(b)(2) only when it addresses electrical hazards and incorporates the additional conditions in Note 2.
- A locked breaker does not prove the absence of voltage. A qualified person must perform the checks required by 1910.333(b)(2)(iv).
Which OSHA Rule Applies? Start With the Hazard
Quick answer: Use 1910.333 for applicable electrical work practices and 1910.147 for covered machine servicing and hazardous-energy control. A task can involve both. One procedure can satisfy both only when it meets Note 2 to 1910.333(b)(2).
Start by identifying the task, the parts employees may be exposed to, and every energy source that could cause movement, startup, or release. Electrical exposure and machine-servicing hazards can exist at the same time.
OSHA 1910.333 vs. 1910.147 at a Glance
| Aspect | OSHA 1910.333 | OSHA 1910.147 |
|---|---|---|
| Primary focus | Electrical safety-related work practices under Subpart S | Control of hazardous energy during covered machine servicing and maintenance |
| Typical application | Work on or near exposed electrical parts and fixed electric equipment or circuits | Servicing or maintenance where unexpected startup, energization, or stored-energy release could injure employees |
| Isolation and control | Disconnect electrical sources, control stored energy, apply locks/tags as required, and follow electrical-specific provisions | Follow the energy-control program and equipment-specific procedure to isolate all hazardous energy sources |
| Verification | A qualified person performs the restart check and tests exposed circuit parts for absence of voltage, including induced voltage and backfeed | An authorized employee verifies the machine or equipment is isolated and deenergized under 1910.147(d)(6) |
The table is a starting point. The exact requirements still depend on the equipment, task, and workplace.
What Does OSHA 1910.333 Cover?
OSHA 1910.333, “Selection and use of work practices,” is part of Subpart S, Electrical. It addresses work on or near equipment or circuits that are, or may be, energized. Under 1910.333(a)(1), exposed live parts generally must be deenergized before work, subject to limited exceptions where deenergizing would introduce additional hazards or is infeasible because of equipment design or operational limits.
For work on exposed deenergized parts, 1910.333(b)(2) sets the lockout and tagging requirements for fixed electric equipment and circuits. “Fixed” equipment means equipment fastened in place or connected by permanent wiring methods. The rule requires its steps to be followed in order.
What the electrical lockout sequence requires
- Plan safe procedures before deenergizing the equipment.
- Disconnect all electric energy sources. Push buttons, selector switches, and interlocks cannot be the sole means of deenergization.
- Release hazardous stored electrical energy and block or relieve stored non-electrical energy that could reenergize the circuit.
- Apply locks and tags to the disconnecting means, subject to the specific exceptions in 1910.333(b)(2)(iii).
- Have a qualified person verify that the equipment cannot be restarted and test the circuit parts employees may be exposed to.
Employers must maintain a written copy of these procedures. The rule also sets requirements for safe reenergization, including confirming tools and temporary protective devices have been removed, warning exposed employees, and controlling lock and tag removal.

What Does OSHA 1910.147 Cover?
OSHA 1910.147, “The control of hazardous energy (lockout/tagout),” applies to servicing and maintenance of machines and equipment when unexpected energization or startup, or release of stored energy, could injure employees. Energy sources include electrical, mechanical, hydraulic, pneumatic, chemical, thermal, and other forms of energy.
The standard requires an energy-control program with procedures, employee training, and periodic inspections. For covered work, authorized employees shut down equipment, isolate energy sources, apply lockout or an allowed tagout system, control stored energy, and verify isolation before servicing.
One important exclusion is exposure to electrical hazards from work on, near, or with conductors or equipment in electric-utilization installations. OSHA addresses those electrical work practices under Subpart S. That does not make 1910.147 irrelevant whenever a machine uses electricity. Other hazardous energy sources on the same machine may still need to be controlled under 1910.147.
For the broader general-industry energy-control program, see TRADESAFE’s summary of OSHA 1910.147.
When Can One 1910.147 Procedure Satisfy 1910.333?
Note 2 to 1910.333(b)(2) allows procedures that comply with 1910.147(c) through (f) to also satisfy 1910.333(b)(2), but only when both conditions are met:
- The procedure addresses the electrical safety hazards covered by Subpart S.
- The procedure incorporates 1910.333(b)(2)(iii)(D), which adds a safety measure for permitted tag-only use, and 1910.333(b)(2)(iv)(B), which requires qualified-person electrical testing.
This cross-reference allows a coordinated procedure rather than two disconnected processes. It does not mean that any general LOTO procedure automatically satisfies the electrical rule.
Important: Applying a lock to a breaker is not the same as verifying that exposed circuit parts are deenergized. The qualified-person verification step remains essential.
How to Decide What Your Facility Needs
Before work begins, safety and maintenance teams should answer these questions and reflect the answers in the applicable written procedure:
- Define the task and identify the parts employees may contact.
- Map every energy source, including electrical supply, stored energy, pressure, movement, and gravity.
- Confirm the workplace and regulatory scope. This article focuses on general industry; construction and electric-utility work may be subject to other standards.
- Identify each isolation point and confirm the device physically disconnects or blocks the relevant source.
- Document responsibilities, stored-energy controls, and the method for verifying isolation.
- Before exposure, ensure a qualified person completes the electrical checks required by 1910.333(b)(2)(iv).

What Verification Looks Like in Practice
Under 1910.147(d)(6), the authorized employee verifies that the machine or equipment has been isolated and deenergized. Under 1910.333(b)(2)(iv), a qualified person must also verify that the equipment cannot be restarted and test the circuit elements and electrical parts employees may be exposed to.
The electrical test must account for induced voltage and unrelated voltage backfeed. A breaker handle in the OFF position, a lock on the disconnect, an indicator light, or a machine that does not start during a tryout does not independently establish that exposed circuit parts are deenergized.
A compatible circuit breaker lockout can help prevent operation of the breaker, but it does not perform the required electrical test. For device selection and installation considerations, see the TRADESAFE circuit breaker lockout installation guide and circuit breaker lockout collection. Confirm the exact breaker model and device fit before recommending a specific product.

Lockout and Tagging: The Exceptions Are Not Interchangeable
Both standards generally favor physical lockout where it can be used, but their tagout provisions differ. Under 1910.147(c)(2), an energy-isolating device that can be locked out must generally be locked out unless the employer demonstrates full employee protection through a tagout system. Under 1910.333(b)(2)(iii), a lock and a tag are generally applied to each disconnecting means, with defined exceptions.
Under 1910.333, tag-only use requires an additional safety measure when permitted. Lock-only use is allowed only when all three conditions are met: one circuit or piece of equipment is deenergized, the lockout period does not extend beyond the work shift, and exposed employees are familiar with the procedure.
An August 17, 2026 OSHA interpretation addressed a lock bearing a permanently affixed, legible label prohibiting unauthorized operation of the disconnecting means and unauthorized removal of the lock. OSHA concluded that the described label would satisfy 1910.333(b)(2)(iii)(A) and (B). This is limited to the circumstances addressed in the letter and does not remove the other lockout, stored-energy, or verification requirements.
Where Does NFPA 70E Fit?
NFPA 70E is a consensus standard for workplace electrical safety, not itself a federal OSHA regulation. The 2027 edition is current. It provides a framework for electrical risk assessment and safe work practices, including establishing an electrically safe work condition and addressing shock and arc-flash hazards.
Use NFPA 70E alongside applicable OSHA requirements, not as a replacement for them. Check clause-level requirements against an authorized copy of the 2027 edition before adding them to a procedure or training material. TRADESAFE’s separate NFPA 70E overview explains the standard’s broader role.
Construction electrical circuits and electric-utility operations may be subject to separate requirements, including OSHA 1926.417 and 1910.269. Confirm the applicable industry and work scope before applying a general-industry procedure.
Three Examples: How the Rules Apply to Real Work
Servicing a motor-driven conveyor
A conveyor has electrical power, pneumatic actuators, and moving parts that could shift under gravity. The servicing procedure must address the hazardous energy sources under 1910.147. If employees may be exposed to fixed electrical circuit parts, the electrical isolation and verification requirements in 1910.333 must also be addressed.
Working inside an electrical panelboard
For work on panelboard wiring, 1910.333 is central to the electrical hazard. A compatible breaker lockout may secure the disconnecting means, but it does not establish absence of voltage at the parts employees may contact. A qualified person must perform the checks required by 1910.333(b)(2)(iv).
Servicing cord-and-plug equipment
1910.147 has a limited exception when unplugging controls the hazardous energy and the plug remains under the exclusive control of the employee performing the work. If either condition is missing, the exception does not apply. Other energy sources still need to be evaluated.
Common Rule-Selection Mistakes to Avoid
- Treating 1910.147 as a substitute for 1910.333 when employees may be exposed to electrical hazards covered by Subpart S.
- Assuming a breaker lock, OFF indicator, or equipment tryout proves absence of voltage.
- Using tag-only methods without meeting the applicable additional-safety-measure or equivalent-protection requirements.
- Applying the cord-and-plug exception without confirming both conditions.
- Calling NFPA 70E a federal OSHA regulation or recommending a breaker lockout without confirming device compatibility.
Make the Procedure Match the Work
The right approach starts with the task and the hazards, not with choosing one regulation number. OSHA 1910.147 controls hazardous energy during covered machine servicing and maintenance. OSHA 1910.333 addresses electrical work practices and the lockout and tagging of fixed electrical equipment and circuits. When both hazards are present, the procedure must account for both. A procedure that relies on 1910.147 to satisfy 1910.333 must meet Note 2, including qualified-person electrical verification.
Before work begins, confirm the scope, identify every energy source, select compatible isolation devices, follow the employer’s written procedure, and complete the required verification. For electrical exposure covered by Subpart S, OSHA 1910.333 remains central even when a coordinated LOTO procedure is used.
Frequently Asked Questions
Does OSHA 1910.147 apply to electrical work?
It can apply to covered machine servicing and associated hazardous energy sources. However, it excludes exposure to electrical hazards from work on, near, or with conductors or equipment in electric-utilization installations covered by Subpart S. OSHA 1910.333 addresses those electrical work practices.
Can one lockout/tagout procedure satisfy both 1910.333 and 1910.147?
Yes, when the procedure complies with 1910.147(c) through (f), addresses the electrical hazards covered by Subpart S, and incorporates the additional requirements in 1910.333(b)(2)(iii)(D) and (iv)(B). A generic machine LOTO procedure does not automatically meet these conditions.
Does 1910.333 require both a lock and a tag?
Generally, yes. The standard includes defined exceptions, including a tag-only method with an additional safety measure and a limited lock-only method when all stated conditions are met.
Who verifies that electrical equipment is deenergized?
A qualified person must perform the checks in 1910.333(b)(2)(iv), including verifying that the equipment cannot be restarted and testing exposed circuit elements and equipment parts for deenergization. The test must account for induced voltage and unrelated voltage backfeed.
Is NFPA 70E mandatory under OSHA?
NFPA 70E is a consensus standard, not itself a federal OSHA regulation. An employer may adopt it as part of its electrical safety program, and it may be required by other applicable obligations. Employers must still comply with the OSHA standards that apply to their work.